Technical FAQs

Ask a Question

Can the existing Full Function Test Kit (FFTK) be used for testing the new Compact NSX MCCB?
Compact NSX can be tested with a new dedicated test kit, Maintenance case reference TRV00910. This TRV00910 test kit works in association with the...
Can the same mechanical interlock for LC1FL44 contactor be used for mechanical interlock of the new equivalent LC1F6304 contactor.
Yes, the same mechanical interlock LA9FL970 can be used for both the old LC1FL44 as well as for new equivalent LC1F6304 contactors. This is a horizontally...
What are the recommended Cable Sizes and the Tightening Torque values for the Multi9 Final Low Voltage (FLV) range of products?
The recommended Cable Sizes and the Tightening Torque values for the Multi9 Final Low Voltage (FLV) range of products is given in the attached document....
What is the difference between 31088 and 31097 key locking devices.
31097 key locking device is used for the Single Handle Source Changeover Assembly in which different type off cam is used. These cams are to be ordered...
Can the OA1 output of Tesys U be used with multi function unit to drive a separate motor contactor.
Output OA1 for Tesys U with base contactor (LUB**) is only used to drive the contactor embedded inside the TesysU contactor base LUB.   In order to use...
What is the new tag point count licensing in Citect SCADA V7.0 ?
In CitectSCADA 6.10 or earlier, multiple tags that share the same I/O device address will be counted as a single I/O point. This is calculated at...
Which Modbus functions are used for reading/writing multiple data on IO scanning in Modicon Quantum range.
In Modicon Quantum range, I/O scanning works with following Modbus function codes:   FC3 for Reading Multiple 4X registers. FC16 for Writing Multiple...
What are the part reference for the Magelis XBT GT series CF card.
The part reference for the Magelis XBT GT series CF cards are as tabulated below :   Memory Size Part Reference 128 MB XBTZGM128 256 MB XBTZGM256...
Which are the latest GSD file revisions for ProfibusDP communication board of the Altivar 71 Drive.
The latest GSD File revisions required for ProfibusDP communication board of the Altivar 71 Drive are as follows:  1. The correct revision of GSD...
What is the meaning of fault code 151 in XXMIT block in Unity Pro.
The fault code 151 means that MsgOut is smaller than 12 Byte when 'Modbus Master Messaging' function is selected. To prevent this fault do the following:...
Results 1 - 10 of 100